NCE PS2
Esecuzione
Energy saving variable speed circulating pump driven by a permanent magnet synchronous motor (pm) controlled by on board inverter.
Bronze pump casing.
Applicazioni
Sanitary hot water systems.
Limiti impiego
Liquid temperature from +5 °C to +65 °C
— Ambient temperature from 0 °C to +40 °C
Maximum permissible working pressure: 3 bar
Storage: -10°C/+50°C max. relative humidity 95% at 40 °C
— Certifications: in conformity with CE requirements
Sound pressure ≤ 45 dB (A).
— Minimum suction pressure: — 0,05 bar at 75 °C 0,28 bar a 90 °C.
EMC secondo: EN 55014-1, EN 55014-2, EN 61000-3-2, EN 61000-3-3.
Connections: threaded ports ISO 228: G 1.
Motore
Synchronous motor with permanent magnet.
— Motor: variable speed
— Standard voltage: single-phase 230 V (-10%;+6%)
— Frequency: 50/60 Hz
— Protection: IP 44
— Insulation class: F
— Class II appliance
Overload protection (integrated).
— Cable: phases and neutral.
Constructed in accordance with EN 60335-1, EN 60335-2-51.